Search:  
 
 

topPower Converter Characteristics

SM2 Magnet
SM2
NR41-01 CLEMESSY
Power In 3 ~ 18kV/7200A
Power Out 6000A/600V
Converter Type Thyristors 12P
Control type Front end VME

topOperation Responsibles

1st Intervention Piquet Area icon Piquet TE-EPC Experimental Areas(163668)
Responsibles: Yves GAILLARD Yves GAILLARD
Xavier GENILLON Xavier GENILLON

topPower Converter Architecture

SM2 magnet is located on M2 beam line inside PPE221 zone.

SM2 architecture

SM2 power converter architecture

topPower Part

SM2 magnet is supplied by the NR41-01 power converter.

topControl & Regulation Part

SM2 control synoptique

SM2 control synoptique

The contol system is managed by an old SPS Main Bends electonics for the interlocks, an old SPS Aux PS electronics for the regulation and a converter crate modified from the North area.

The bending magnets B4 and B5 of M2 beam line needs to be interlocked with SM1 and SM2 spectrometers. To manage this functionality, the power converters of B4, B5, SM1 and SM2 are interconnected.

topMagnet Protection

Magnet protection is standard.

topMagnet connection

SM2 Magnet connection

SM2 Magnet connection simplified schematic

topMagnet Types

  • SM2 coil + DC Cables: R= 0.114 ohm

topMachine Installation

    SM2 power converter is installed in North area:

  • 891 (BA82): 1

topProduction Contract & Contract History

  • Manufacturer: CLEMESSY
  • Production year: 1980